mharb 3f5796efa2 v0.4
Signed-off-by: mharb <mharb@noreply.localhost>
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00
2026-10-13 21:27:01 +00:00

ModPulse

ModPulse is a local-first Modbus TCP monitoring and control application. It polls configured stations and devices, converts register values into operator-readable measurements, records history in SQLite, evaluates rules, and presents live status in a browser-based console.

This README is the project’s single maintained guide for operators, controls engineers, integrators, and developers. Instructions and limits below describe the checked-in implementation; verify device-specific settings against the equipment manual before connecting real hardware.

ModPulse operator console tour: live Overview, Devices, Discovery, Trends, and System workflows

Start here

What you need

  • .NET SDK 10.0.302 (the SDK selected by global.json; a compatible later 10.0 SDK is accepted).
  • Bash and curl for the local scripts.
  • For browser tests or the UI tour: Node.js 18+, npm dependencies, and Playwright’s Chromium browser.
  • Docker Engine and Docker Compose only if using the container workflow.

Build on Windows with PowerShell

  1. Install the .NET 10 SDK. The repository pins SDK 10.0.302 in global.json; install that version or a compatible later .NET 10 SDK.
  2. Extract the ZIP to a writable folder (avoid deeply nested paths), then open PowerShell in the extracted ModPulse folder.
  3. Build the whole solution:
dotnet --version
dotnet build .\ModPulse.sln -c Release --nologo

Or use the included build-only helper:

.\deploy.ps1 -DeploymentType build-only

If Windows blocks local scripts, run that command for this process only:

powershell.exe -NoProfile -ExecutionPolicy Bypass -File .\deploy.ps1 -DeploymentType build-only

After building, run the bundled simulator and web app together with .\start.ps1 local; open http://localhost:5000 and stop with Ctrl+C. This runs in Development mode and does not seed the pilot dataset automatically. .\start.ps1 docker requires Docker Desktop with Compose. Native Windows builds use framework-dependent net10.0 outputs; this source archive does not include binaries.

The shareable source archive is generated locally as artifacts/ModPulse-windows-source.zip (git-ignored build output, not committed). It contains the current source tree and README, not Git history, local configuration/secrets, build outputs, or local databases. Generate it with git ls-files -z | tar --null -T - -czf artifacts/ModPulse-windows-source.tgz or the equivalent zip step, then verify no .env, *.db, or data/ contents are included.

Run a local simulator and app

From the repository root:

./start.sh local

This builds Release binaries, starts the bundled simulator, then runs the API/UI in the foreground. Open http://localhost:5000. The simulator exposes Modbus TCP at port 10502 and its health/control API at 5001. Press Ctrl+C to stop the API and its simulator child process.

The local run uses ./data by default. It is persistent: stopping the app does not erase configuration or history. For a clean demo, use a new data directory rather than deleting a directory whose contents you need:

DataDirectory=/tmp/modpulse-demo-data ./start.sh local

To load a ready-to-use pilot-plant configuration, start ModPulse first, then in another terminal run:

MODPULSE_API_URL=http://localhost:5000 \
SIMULATOR_ENDPOINT=localhost:10502 \
bash seed_uat_data.sh

This creates one plant-floor master, five simulated devices, their register maps, and two example conditional rules. It is safe to rerun against the same database. The seed writes to the API’s configured database; it does not clear existing data. Use a disposable DataDirectory if you want an isolated demo.

Confirm both processes are ready:

curl -fsS http://localhost:5001/health
curl -fsS http://localhost:5000/health

The first endpoint returns {"status":"Healthy"}; the API returns runtime and database metrics. A healthy service alone does not prove a field device or every configured tag is communicating.

Run with Docker Compose

./start.sh docker

The script generates an untracked .env file with a random key if one is absent, then builds and starts the Compose stack. The UI/API is at http://localhost:5000; simulator REST and Modbus TCP ports are 5001 and 10502. Stop with:

./start.sh down

The stack stores data in the named Docker volume modpulse-data. ./start.sh clean also removes local build/database output and Docker volumes; it is destructive and should only be used when you intentionally want to discard local data.

For an explicit environment setup, copy .env.example to .env, set a long random MODPULSE_API_KEY, then use docker compose up --build. Keep .env private and untracked. The Compose file fails instead of substituting a public default when the key is empty.

First operator workflow

The console is organized around the function keys F1–F5 (the corresponding buttons also work with a mouse):

Page What it is for
F1 Overview Current point values, quality/status, alarms, station/device context, and change-rate window.
F2 Devices Configure a station (Modbus master), its devices (unit/slave IDs), and each device’s register maps (tags). Test a configured register and perform supported writes.
F3 Discovery Scan an authorized subnet for Modbus TCP hosts, scan a configured station for unit IDs, and optionally probe candidate registers.
F4 Trends Select one device and one tag, choose a time window, query historical samples, and inspect the chart/table.
F5 System Review/configure rules; view rule execution logs and audit history; export CSV; inspect client-link and queue status/settings.

The System page has Rules, Event Log, Audit, Export, and Settings subpages. The app’s appearance can be toggled between light and dark in the header.

Configure real equipment

Start with the simulator and a small, read-only set of tags. Before connecting a production PLC, RTU, or gateway, verify its network route, firewall rules, Modbus TCP port, unit ID, register reference convention, function code, data type, word/byte order, and permissible polling rate with the device documentation and controls owner.

  1. On Devices, add a Station. Give it a recognizable plant/line name, choose the supported connection type, enter the Modbus endpoint (usually host:502 for standard Modbus TCP), and set a poll interval and timeout appropriate to the equipment.
  2. Add a Device beneath that station. Its unit/slave ID must match the endpoint’s configured unit ID. Use a human name such as Boiler Feed Pump rather than a generic label.
  3. Add one Register per meaningful signal. Set name, function code, zero-based protocol address, count, data type, units, scale/offset, poll interval, historian deadband, maximum log interval, and active state.
  4. Save the map and use Test where available. Compare the raw/engineering result with a trusted display or a known simulator value before enabling a larger map.
  5. Confirm the point appears on Overview, updates, and has sensible quality/status. Use Trends after history samples have accumulated.
  6. Add conditional rules only after validating the point and safe action. Test alarms/actions with a simulator or an approved non-production target first.

Addressing: Modbus protocol addresses are generally zero-based, while vendor manuals often show references such as 40001. A common convention maps 40001 to protocol address 0, but vendors vary; do not blindly subtract one. For a 32-bit or 64-bit value, the map must request enough adjacent 16-bit registers. Confirm word order and floating-point representation for the particular device. ModPulse’s numeric converter interprets multi-register values in big-endian word order; it does not offer per-tag byte/word-swap configuration.

Scaling: The intended engineering calculation is decoded raw value × scale factor + offset. Apply scale only when the device map confirms it (for example, an integer tenths-of-a-degree register may use scale 0.1). Do not apply scale to a register already reported in engineering units.

Polling and history are different: The station poll interval sets the fastest scan cadence. A tag may poll more slowly. Historian deadband suppresses repeated near-identical samples, while maximum log interval forces periodic retention of a stable value. Live display updates are independent of whether every poll creates a history row.

Example pilot map

seed_uat_data.sh creates a simulator-backed example with:

Simulated asset Example tags
Press line PLC, unit 1 CPU temperature/load, memory use, cycle time
Extruder drive, unit 2 Motor speed/current, DC bus voltage
Barrel transmitter, unit 3 Barrel-zone temperature
Hydraulic transmitter, unit 4 Hydraulic pressure
Coolant flow meter, unit 5 Flow rate and totalizer

The simulator generates changing process-like values with device-specific operating ranges and noise. They are synthetic test data, not calibration values, safety limits, or evidence of real field-device compatibility.

Simulator use and fault testing

The .NET simulator provides deterministic sample devices with changing values and fault controls. Its defaults are Modbus TCP port 10502, REST port 5001, device count 25, seed 42, and update cadence 500 ms (the Docker image configures 10 devices). Runtime environment/configuration can override these values, including Simulator__Port, Simulator__DeviceCount, Simulator__Seed, and Simulator__UpdateCadenceMs.

Useful simulator endpoints:

curl http://localhost:5001/health
curl http://localhost:5001/devices
curl -X POST http://localhost:5001/devices/1/inject-failure \
  -H 'Content-Type: application/json' \
  -d '{"type":"timeout","duration":10}'
curl -X POST http://localhost:5001/devices/1/recover
curl -X POST 'http://localhost:5001/devices/1/registers/100?value=42.5'

The exact accepted failure modes are defined by src/ModPulse.Simulator; inspect that implementation before building automation around a fault type. Manual register overrides are temporary and the simulation resumes after the configured hold period. Keep the simulator and its REST endpoint on a trusted local/test network.

There is also a Python simulator under simulator/ with dependencies in simulator/requirements.txt; the primary scripts and current .NET integration/UAT runs use src/ModPulse.Simulator.

How the pieces fit

Modbus TCP devices  <->  ModPulse Engine  <->  SQLite config/history
                              ^
                              |
Browser  <->  API + static UI + SignalR
  • Core (src/ModPulse.Core/): domain models, enums, interfaces, numeric conversion, and request validation.
  • Data (src/ModPulse.Data/): EF Core SQLite contexts and repositories.
  • Engine (src/ModPulse.Engine/): polling, rule evaluation, logging/maintenance, Modbus communication, and notifications.
  • API (src/ModPulse.Api/): CRUD/data/health/discovery endpoints, SignalR hub, and static UI serving.
  • Web (src/ModPulse.Web/wwwroot/): browser application; it is served by the API and needs no separate frontend server.
  • Engine service (src/ModPulse.EngineService/): headless host for background engine services.
  • Simulator (src/ModPulse.Simulator/): Modbus TCP test server plus health, data, and fault-control REST endpoints.

Configuration and history are stored in config.db and logs.db under DataDirectory (default ./data). Keep backups of both databases. Stop writers or use SQLite’s supported backup mechanism rather than copying only a live database file; WAL sidecars may contain committed data not yet folded into the main file.

Configuration and safe sharing

Settings are read from appsettings JSON files and environment variables. Common settings:

Setting Purpose
ASPNETCORE_ENVIRONMENT Development or Production; local start.sh defaults to Development.
ASPNETCORE_URLS API or simulator HTTP bind address.
DataDirectory Directory for the SQLite databases.
MODPULSE_API_KEY Required to be non-empty at API startup outside Development.
Webhook__Url / WEBHOOK_URL Optional rule notification destination.
Simulator__Port / SIMULATOR_PORT Simulator Modbus TCP port (the UAT runner uses SIMULATOR_PORT).
SIMULATOR_API_PORT Simulator REST API port used by repository scripts.

Never commit .env, real API keys, certificates/private keys, database files, or customer-specific device maps. .env.example contains no credential. Deployment scripts create random .env keys; review generated configuration locally and manage production secrets through your deployment platform where available. Rotate any credential that has ever been committed or shared.

Security limitation: although the API requires MODPULSE_API_KEY to be set at production startup and the browser sends an X-API-Key header, the current API code does not validate that header on incoming requests. There is no user/role/permission system. Do not treat the setting as effective authentication or expose this build to an untrusted network; use an appropriately secured, restricted environment until access control has been implemented and tested. The bundled simulator’s REST control endpoints are also unauthenticated and must remain on a trusted network.

API quick reference

The source of truth is src/ModPulse.Api/Endpoints/ApiEndpoints.cs. CRUD collections use the listed GET, POST, PUT /{id}, and DELETE /{id} patterns unless noted.

Area Routes
Masters /api/masters, /api/masters/{id}
Devices/slaves /api/slaves, /api/slaves/{id}, /api/masters/{masterId}/slaves
Register maps /api/registermaps, /api/registermaps/{id}, POST /api/registermaps/{id}/test, POST /api/registermaps/{id}/write
Templates /api/templates, /api/templates/{id}, POST /api/slaves/{slaveId}/apply-template/{templateId}
Rules /api/rules, /api/rules/{id}, POST /api/rules/{id}/trigger
Discovery POST /api/discovery/network-scan?subnet=…&port=…, POST /api/discovery/scan/{masterId}, POST /api/discovery/probe/{masterId}/{slaveId}, POST /api/discovery/save/{masterId}, POST /api/discovery/autopopulate/{slaveId}
Data GET /api/data/{slaveId}/{registerMapId}/latest, /history, /api/data/recent, /api/data/pulse-logs, /api/data/partitions
Audit/export GET /api/audit, /api/audit/export, /api/data/{deviceId}/{regId}/export
Health GET /health, GET /api/health
Realtime SignalR hub /hub/modbus

History defaults to the previous day and 1,000 rows; requested limits must be 1–10,000 and history windows cannot exceed five years. Discovery scans actively probe networks/devices: only run them on subnets and equipment you are authorized to scan.

Build, tests, and UI tour

Build the solution:

dotnet build ModPulse.sln -c Release --nologo

Run the .NET suite with a simulator:

./run-tests.sh

Run the complete browser suite:

./run_all_uat.sh

run_all_uat.sh builds unless SKIP_BUILD=1, starts isolated simulator/API processes with ephemeral ports and a temporary database, seeds the pilot plant, runs all uat/*.spec.js files serially in Chromium, and cleans up afterward. It leaves the default ./data databases and any separately running local app alone. If iterating after a successful build, SKIP_BUILD=1 skips only the build; the isolated services and data seed still run. Override browser concurrency with PLAYWRIGHT_WORKERS, but the default is one because journeys share mutable app state.

Run focused journeys:

./run_all_uat.sh uat/00-smoke-user-journeys.spec.js
./run_all_uat.sh uat/07-exploratory-operator-journeys.spec.js --reporter=list
./run-e2e-tests.sh

The .NET tests cover API contracts/validation, Modbus decoding and polling, persistence, rules, logging, and failure handling. Playwright tests cover smoke/onboarding journeys, operator workflows, responsive UI, trends, navigation, and deadlock/softlock behavior through browser interaction. Three intentionally skipped journeys document unimplemented product gaps: multi-tag trend overlays, bulk register-map import, and user/role management. A skipped workflow is not tested feature coverage.

The UI tour GIF above is generated from the running app against the simulator and seeded sample data. To install the browser dependency if missing:

npm ci
npx playwright install chromium

Repository map

src/ModPulse.Api/          API host, endpoints, SignalR
src/ModPulse.Core/         domain models, validation, conversion
src/ModPulse.Data/         SQLite contexts and repositories
src/ModPulse.Engine/       polling, logging, rules, Modbus
src/ModPulse.EngineService/Headless engine host
src/ModPulse.Simulator/    .NET Modbus TCP simulator
src/ModPulse.Web/          UI assets served by the API
simulator/                 Optional Python simulator
tests/                     .NET tests
uat/                       Playwright browser journeys
deploy/                    Container and service deployment files

Troubleshooting

Port is already in use: local quick start expects 5000, 5001, and 10502. Stop only the ModPulse process you started, or use the test harness, which chooses ephemeral ports. Do not kill unrelated processes to free ports.

Simulator health fails: check that the simulator process started and that 5001 is reachable; check the Modbus TCP port in the configured master and SIMULATOR_PORT.

API/UI does not open: check http://localhost:5000/health, API startup output, ASPNETCORE_URLS, and whether another process owns port 5000.

Live values are missing: confirm a master is active and points to the correct host/port; verify the device unit ID, active state, register function/address/count/type, and simulator/field-device reachability. Confirm the API’s DataDirectory is the database you seeded or configured. A successful health check does not guarantee a successful Modbus read.

No trend samples yet: history is created by polling and may be suppressed by deadband until the maximum log interval. Wait for collection, query a matching device/tag and date range, and confirm the tag is active.

Browser test cannot launch Chromium: install it with npx playwright install chromium and install the host OS dependencies if Playwright reports missing libraries.

Resetting a demo: point DataDirectory to a new disposable directory. Avoid ./start.sh clean unless you intend to remove local build/database artifacts and Docker volumes.

Project status

The simulator-backed build and tests are useful development and pilot evidence, not certification or proof of production readiness. Validate against target hardware and review deployment security, backups/restores, upgrade/rollback, monitoring, capacity, and operational support before production use.

S
Description
A lean, high-performance headless Modbus TCP/RTU data-logger and pulse-controller with a single-page web GUI
Readme GPL-2.0