$OpenBSD: README-main,v 1.3 2012/11/08 21:59:01 sthen Exp $
|
|
|
|
+-----------------------------------------------------------------------
|
|
| Running ${FULLPKGNAME} on OpenBSD
|
|
+-----------------------------------------------------------------------
|
|
|
|
NUT is split into separate components. A hardware driver interfaces
|
|
with the device and sends information to upsd. A monitor (upsmon)
|
|
connects to upsd and shuts down the machine when necessary.
|
|
|
|
These components can reside on separate computers (i.e. UPS monitored
|
|
by various computers may communicate with a central upsd, and a whole
|
|
network may run upsmon to allow for shutdown).
|
|
|
|
On OpenBSD, daemons from packages are usually started by adding to the
|
|
pkg_scripts variable in /etc/rc.conf.local. For NUT, machines running
|
|
upsd or the hardware driver should include "upsd" in this line, and all
|
|
machines should include "upsmon". Where you run both, upsd should
|
|
be started first. For example you could use this line:
|
|
|
|
pkg_scripts="upsd upsmon [...any other daemons...]"
|
|
|
|
Network devices
|
|
---------------
|
|
To reduce dependencies for the basic NUT package, some network devices
|
|
are supported by optional subpackages: nut-snmp (for SNMP-based devices),
|
|
nut-xml (for Eaton/MGE devices using an XML/HTTP protocol).
|
|
|
|
Connecting to a remote server running nutd(8) requires only the basic
|
|
NUT package which also includes the file you are reading now.
|
|
|
|
Configuring NUT
|
|
---------------
|
|
The following files must be edited for a typical installation.
|
|
|
|
* ups.conf
|
|
|
|
Details of UPS device/s are held here. These may either be directly
|
|
connected, or network devices (this can include a NUT server running on
|
|
another machine). Configuration sections for this file can be generated
|
|
for network and USB devices using nut-scanner(8). This is in the main
|
|
NUT package but picks up dependencies at runtime, so if you wish
|
|
to scan for network devices, just make sure the relevant package
|
|
is installed before you run the scanner.
|
|
|
|
To scan for network devices, specify start and end IP addresses:
|
|
|
|
# nut-scanner -s 192.168.17.1 -e 192.168.17.20
|
|
|
|
* upsd.users
|
|
|
|
upsd(8) user authentication is configured here.
|
|
|
|
* upsmon.conf
|
|
|
|
This file informs upsmon(8) which devices (configured in ups.conf) it
|
|
should monitor. It also contains passwords to authenticate to upsd(8).
|
|
|
|
Device permissions
|
|
------------------
|
|
For locally connected UPS devices, the userid running NUT (normally
|
|
${NUT_USER}) must have access to the relevant device nodes.
|
|
|
|
RS232: Either add ${NUT_USER} to group "dialer" or change the group
|
|
ownership of the relevant /dev/tty* device to ${NUT_USER}.
|
|
|
|
USB: Change the group of the relevant /dev/ugen* and /dev/usb* devices
|
|
to ${NUT_USER}; to identify the specific controller and ugen device
|
|
names, use "sudo usbdevs -vd".
|
|
|
|
Starting the daemons
|
|
--------------------
|
|
To start the daemons without rebooting you can use:
|
|
|
|
# /etc/rc.d/upsd start
|
|
# /etc/rc.d/upsmon start
|
|
|
|
It is recommended that you test a full cycle of rebooting, checking
|
|
that the daemons are running correctly ("upsc <upsname>" will display
|
|
information retrieved by NUT from the UPS), allowing the machine
|
|
to be shut down by the UPS, and returning power.
|